Did You Know...

That Liquid Tight Connectors Can Be Used For Class 1, Div 2 Locations

February 15, 1999



The National Electrical Code (NEC) section 501-16 (b), exception 'a', will permit the use of liquidtight flexible metal conduit and liquidtight connectors to be the sole equipment grounding conductor in Class 1, Division 2 locations. However, strict requirements must be met:

  • Conduit and connectors must be UL listed.
  • Conduit cannot exceed 6 feet in length.
  • Overcurrent protection in the circuit is limited to 10 amperes or less.
  • It supplies other than power utilization loads.



Always use Bridgeport's UL listed Liquidtight Connectors.





Note: Above comments are not an interpretation of the National Electrical Code or local regulations. Always consult your local electrical inspector for requirements in your area.